Technical Specifications Octalarm alarm diallers

System properties

Contact inputs

DescriptionSpecification
Voltage30VDC Max
Vil<3V
Vih>4V
Note- 10k pull-up to 12VDC
- Input can be a contact to GND or voltage

Relay contact

DescriptionSpecification
Max. load30VDC / 2A, 30VAC / 1A (resistive load)

Open-drain output

DescriptionSpecification
Max. switch voltage12V/300mA
Output voltage12V/120mA
ProtectionShort circuit, thermal

USB (master)

DescriptionSpecification
Type2.0
Load5V/500mA

Applies ONLY to the Touch

I/O bus

DescriptionSpecification
Output voltage12V/100mA
DriverISL3152 with ‘external fail-safe biasing’

PSTN

DescriptionSpecification
‘Line’RJ11
‘Phone’RJ11

Ethernet

DescriptionSpecification
Type10Base-T/ 100Base-T
Auto MDIXYes
Required useIndoor

For reliable alerts, a stable internet connection is required. If you are using a firewall in the company network, please refer to the information on What to do in case of a firewall in the company network.

Mobile network (GSM)

DescriptionSpecification
TyresLTE Cat. 4
3G HSPA+
FDD LTE: B1/B3/B5/B7/B8/B20
TDD LTE: B38/B40/B41
WCDMA: B1/B5/B8
GSM: 900/1800
Bandwidth1.4/3/5/10/15/20 MHz
CapacityClass 3 (23dBm±2dB) for LTE FDD
Class 3 (23dBm±2dB) for LTE TDD
Class 3 (24dBm +1/-3dB) for TD-SCDMA
Class 3 (24dBm +1/-3dB) for UMTS
Class E2 (27dBm ±3dB) for EDGE 850/900MHz
Class E2 (26dBm +3/-4dB) for EDGE 1800/1900MHz
Class 4 (33dBm ±2dB) for GSM 850/900MHz
Class 1 (30dBm ±2dB) for GSM 1800/1900MHz

Power supply

DescriptionSpecification
Nominal5 Watt
Max.20 Watt
Imax0.22A
Power supply range100 ... 240VAC +/- 10%, 50/60 Hz

RFID

DescriptionSpecification
Frequency13.56MHz
Max. range10mm

Service Life

DescriptionSpecification
Calculated MTBF10.64 years, as per the ‘parts count’ method

Housing and operating conditions

DescriptionSpecification
HousingWall mount
Dimensions (W X H X D)208 x 242 x 42 (mm)
Weight1360gr (with battery and GSM module)
Operating temperature0°C ... +50°C
Storage temperature0°C ... +85°C
Humidity20% - 80% (non-condensed)
IP codeIP42
Max. heightUp to 2000 metres

Regulations

DescriptionSpecification
EMCEN 301 489-1 V2.1.1 / EN301 489-3 V1.6.1
LVDEN-IEC 62368-1:2014 + AC:2015 + A11:2017 + AC:2017