Technical Specifications EM-8001
System properties
Contact inputs
Description | Specification |
---|---|
Voltage | 30VAC or 30VDC max. |
Vil | <4.4V |
Vih | >4V |
Note | - 10k pull-up to 12VDC - Input can be a contact to GND or voltage |
Relay contact
Description | Specification |
---|---|
Max. load | 30VDC / 1A, 30VAC / 1A (resistive load) |
I/O bus
Description | Specification |
---|---|
Cable type | RS485 Modbus cable (22 AWG) |
Length | < 1km |
Closure | 120Ω |
See Quickstart EM|Wiring diagram EM-8001 to Octalarm alarm dialler for further explanation.
Power (external)
Description | Specification |
---|---|
Consumption | DC: 1 Watt AC: 1.5 Watt (RMS), single-sided rectified 5 Watt (charging capacitor) |
Imax | 0,22A |
Power supply range | 8 - 30VDC 20 - 30VAC |
Note: when using the relay, the power supply must be at least 15VDC.
Service Life
Description | Specification |
---|---|
Calculated MTBF | 10.64 years, as per the ‘parts count’ method |
Housing and operating conditions
Description | Specification |
---|---|
Housing | DIN-Rail (TS35) assembly and wall mounting |
Dimensions (W X H X D) | 71 x 90 x 33 (mm) |
Weight | 135gr |
Operating temperature | -30°C ... +70°C |
Storage temperature | -40°C ... +85°C |
Humidity | 20% - 80% (non-condensed) |
IP code | IP30 |
Max. height | Up to 20,000 metres |
Regulations
Description | Specification |
---|---|
EMC | Emission: EN 55032 (2012) + AC (2013), class B Immunity: EN 55024 (2010), 10Vrms |