Output
The alarm dialler features two open-drain and two relay outputs. You can set this to function as:
-
external buzzer: the external buzzer is configurable at
Alarms
(see Alarms|Configuring inputs: Alarm settings (left-hand side) Buzzer for further explanation). The output follows the alarm buzzer. This means that when the dialler’s buzzer sounds, there is voltage on the output and when it is accepted, no voltage goes across the output. -
external strobe light: when the alarm is active, voltage is applied to the output. The strobe light only deactivates when there is no more alarm.
Outputs overview
Relay contact
Description | Technical specification |
---|---|
Max. load | 30VDC / 2A, 30VAC / 1A (resistive load) |
Open-drain output
Description | Technical specification |
---|---|
Max. switching voltage | 42V/300mA |
Max. load current | 350mA |
Output voltage | 12V/120mA |
Protection | thermal |
Customising outputs
- Go to
Settings
. - In the navigation, scroll to
Outputs
. - Click
Edit
. - Then, where applicable, under open collector and relay outputs, choose None, External buzzer or Stobe light.
- Click
Save
.